siemens触摸屏连接冗余CPU

  1. 1、博图新建连接:
    1. PLC_Changer_12
  • 2、博图新建VB脚本:
  • 3、建立脚本触发:
  • 1、博图新建连接:

    PLC_!

    PLC_2

    PLC_Changer_12

    2、博图新建VB脚本:

    connection_PLC1

    Sub connection_PLC1()
    '提示:
    ' 1. 使用 <CTRL+SPACE> 或 <CTRL+I> 快捷键打开含所有对象和函数的列表
    ' 2. 使用 HMI Runtime 对象写入代码。
    '  示例:HmiRuntime.Screens("Screen_1")。
    ' 3. 使用 <CTRL+J> 快捷键创建对象引用。
    '从此位置起写入代码:
    
    
    '***************************
    '****    Initialization    ****
    '***************************
    'During initialization the default connection is 
    'saved into the memory of connections (connected_to). 
    
    If SmartTags("connected_to") = "" Then
        SmartTags("connected_to") = "PLC_1"
    End If
    
    '*******************
    '****   Reset   ****
    '*******************
    'Reset of connection brake detection for PLC_1
    
    SmartTags("con_state_PLC1") = 1
    
    '*****************************
    '****   Fault detection   ****
    '*****************************
    'Incrementation of the brake detection value for the connection to PLC_2
    
    If SmartTags("con_state_PLC2") <= 10 Then
        SmartTags("con_state_PLC2") = SmartTags("con_state_PLC2") +1
    End If
    
    '**************************
    '****   Switch over    ****
    '**************************
    'is the limit of the status tag for the connection to PLC_2 reached, the connection to PLC_1 will
    'switch the data connection.
    'Function Usage: ChangeConnection Connection, Address, Slot, Rack
    
    If SmartTags("con_state_PLC2") >= 11 Then
        If SmartTags("connected_to") = "PLC_2" Then
            ChangeConnection "PLC_Changer_12", "172.19.43.2", 2, 0
            SmartTags("con_state_PLC2") = 100
            SmartTags("connected_to") = "PLC_1"
        ElseIf SmartTags("connected_to") = "PLC_1" Then
            SmartTags("con_state_PLC2") = 100
        End If
    End If
    
    '***************************
    '****   Reintegration   ****
    '***************************
    'after a full connection brake the first repaired connection will activate the data connection
    
    If SmartTags("connected_to") = "connection lost" Then
        ChangeConnection "PLC_Changer_12", "172.19.43.2", 2, 0
        SmartTags("con_state_PLC2") = 100
        SmartTags("connected_to") = "PLC_1"
    End If
    End Sub
    

    connection_PLC2

    Sub connection_PLC2()
    '提示:
    ' 1. 使用 <CTRL+SPACE> 或 <CTRL+I> 快捷键打开含所有对象和函数的列表
    ' 2. 使用 HMI Runtime 对象写入代码。
    '  示例:HmiRuntime.Screens("Screen_1")。
    ' 3. 使用 <CTRL+J> 快捷键创建对象引用。
    '从此位置起写入代码:
    
    '***************************
    '****    Initialization    ****
    '***************************
    'During initialization the default connection is 
    'saved into the memory of connections (connected_to). 
    
    If SmartTags("connected_to") = "" Then
        SmartTags("connected_to") = "PLC_1"
    End If
    
    
    '*******************
    '****   Reset   ****
    '*******************
    'Reset of connection brake detection for PLC_2
    
    SmartTags("con_state_PLC2") = 1
    
    
    '*****************************
    '****   Fault detection   ****
    '*****************************
    'Incrementation of the brake detection value for the connection to PLC_1
    
    If SmartTags("con_state_PLC1") <= 10 Then
        SmartTags("con_state_PLC1") = SmartTags("con_state_PLC1") +1
    End If
    
    
    '**************************
    '****   switch over    ****
    '**************************
    'Is the limit of the status tag for the connection to PLC_1 reached, 
    'the connection to PLC2 will switch the data connection.
    'Function Usage: ChangeConnection Connection, Address, Slot, Rack
    
    If SmartTags("con_state_PLC1") >= 11 Then
        If SmartTags("connected_to") = "PLC_1" Then
            ChangeConnection "PLC_Changer_12", "172.19.43.1", 2, 1
            SmartTags("con_state_PLC1") = 100
            SmartTags("connected_to") = "PLC_2"
        ElseIf SmartTags("connected_to") = "PLC_2" Then
            SmartTags("con_state_PLC1") = 100
        End If
    End If
    
    
    '***************************
    '****   reintegration   ****
    '***************************
    'After a full connection brake the first repaired connection will activate the data connection.
    
    If SmartTags("connected_to") = "connection lost" Then
        ChangeConnection "PLC_Changer_12", "172.19.43.1", 2, 1
        SmartTags("con_state_PLC1") = 100
        SmartTags("connected_to") = "PLC_2"
    End If
    
    End Sub
    

    connection_lost()

    Sub connection_lost()
    '提示:
    ' 1. 使用 <CTRL+SPACE> 或 <CTRL+I> 快捷键打开含所有对象和函数的列表
    ' 2. 使用 HMI Runtime 对象写入代码。
    '  示例:HmiRuntime.Screens("Screen_1")。
    ' 3. 使用 <CTRL+J> 快捷键创建对象引用。
    '从此位置起写入代码:
    
    '***************************
    '****   Deactivation    ****
    '***************************
    'If the connections are not able to reset there status tag back to "1" they will be marked with 100 (disabled).
    
    If SmartTags("con_state_PLC1") >= 5 Then
        SmartTags("con_state_PLC1") = 100
    End If
    
    If SmartTags("con_state_PLC2") >= 5 Then
        SmartTags("con_state_PLC2") = 100
    End If
    
    'If both connections are marked with "disabled", the connection memory will be set to "connection_lost" 
    
    If SmartTags("con_state_PLC1") = 100 And SmartTags("con_state_PLC2") = 100 Then
        SmartTags("connected_to") = "connection lost"
    End If
    
    '********************************
    '****   Setting fault flag   ****
    '********************************
    'In each cycle of 1 minute the status tags of the connections will be set to 5.
    
    If SmartTags("con_state_PLC1") < 5 Then
        SmartTags("con_state_PLC1") = 5
    End If
    
    If SmartTags("con_state_PLC2") < 5 Then
        SmartTags("con_state_PLC2") = 5
    End If
    
    End Sub
    

    3、建立脚本触发: